YB□ - 12 HIGH/LOW VOLTAGE PREFABRICATED SUBSTATION

This product fully complies with GB17467 'High and Low Voltage Prefabricated Substation' standards. It is suitable for urban public distribution, streetlight distribution, industrial and mining enterprises, urban buildings, residential communities, oil field docks, hotels, parks, and construction sites, and can achieve ring network or terminal power supply methods.

Classification:

Service Hotline:

  • 产品描述
  • Product Introduction

    This product fully complies with GB17467 'High and Low Voltage Prefabricated Substation' standards. It is suitable for urban public distribution, streetlight distribution, industrial and mining enterprises, urban buildings, residential communities, oilfield docks, hotels, parks, and construction sites, and can achieve ring network or terminal power supply modes.

    Product Features

    Diversity: High and low voltage prefabricated substations can be designed according to different high and low voltage layout methods, such as 'grid' structure and '品' structure, to adapt to different application environments and needs.

    Safety: The overall structure is compact and small in size, while the disassembly and installation of various components are convenient, ensuring safe and reliable operation with simple maintenance.

    Protection: The product features complete high and low voltage protection, effectively ensuring the safe operation of the power grid.

    Reliability: Prefabricated substations can select different structural forms and materials according to different usage environments and conditions to meet various usage requirements and ensure the normal operation of the substation.

    Stability: The product is designed for outdoor use, capable of adapting to various outdoor environments, such as harsh climatic conditions and high-altitude areas, thus ensuring a long service life.

    Energy Saving: The transformer room of the prefabricated substation has very low no-load loss, showing significant energy-saving effects, while emitting low harmful gases, resulting in low atmospheric pollution.

    Technical Parameters

    Serial Number

    Name

    Unit

    High Voltage Equipment

    Transformer

    Low Voltage Equipment

    1

    Rated Voltage

    kV

    6/10

    6/0.410/0.4

    0.4

    2

    Rated Capacity

    kVA

     

    50~1600

     

    3

    Rated Current

    A

    200, 400, 630

     

    100~3200

    4

    Rated Short-Circuit Breaking Current

    A

    Load Switch 400-630
    Combination Switch Depends on Fuse

     

    15~63kA

    5

    Rated Short-Time Withstand Current

    kA

    16,20(4s)

     

    15(1s)
    30(1s)

    6

    Rated Peak Withstand Current

    kA

    31.5,50

     

    30
    63

    7

    Power Frequency Withstand Voltage (1min)

    kV

    Relative to Ground and Phase to Phase 32/42

    25/35 (Oil-immersed)

    ≤0.3,2

    Isolation Break 36/48

    20/28 (Dry Type)

    >0.3,2.5

    8

    Lightning Impulse Withstand Voltage (Peak Value)

    kV

    Relative to Ground and Phase to Phase 60/75

    60/75

     

    Isolation Break 70/85

     

    9

    Enclosure Protection Level

     

     

    IP32

     

    10

    Noise Level

    db

     

    55

     

    11

    Implementation Standards

     

    GB/T 17467 'High and Low Voltage Prefabricated Substation'

     

     

    DL/T537 'Technical Conditions for Ordering 6-35kV Box-type Substations'

     

     

    Usage Environmental Conditions

    >Altitude: ≤1000m;
    >Ambient Temperature: -25℃~+40℃;
    >Relative Humidity: Daily average not exceeding 95%, monthly average not exceeding 90%;
    >Seismic Level: Horizontal acceleration 0.4m/s², vertical acceleration 0.15m/s²;
    >Installation site free from severe impact, serious pollution and chemical corrosion, conductive dust, and explosion hazards. If normal usage conditions cannot be met, please consult our company for solutions.

Get A Quote

Note: Please leave your contact information and our professionals will contact you as soon as possible!

Submit

CHAONENG CHARGING (DEZHOU) NEW ENERGY TECHNOLOGY CO., LTD.

Super Charge

Landline:86-4006878001

Sales Phone:86-13255449750

After-sales telephone:86-18988960592

Super Charge

Super Energy Filling Workshop, Xicao Industrial Park, Guoyuan East Road, Songguantun Street, Tianqu New District, Dezhou City, Shandong Province


Message consultation

Filling in your phone and E-mail information will help us to get in touch with you in time and solve your problems as soon as possible.

%{tishi_zhanwei}%

©2024 CHAONENG CHARGING (DEZHOU) NEW ENERGY TECHNOLOGY CO., LTD.

Business License

©2024 CHAONENG CHARGING (DEZHOU) NEW ENERGY TECHNOLOGY CO., LTD.

Business License

Powered by:300.cn